Nexus Cable U 1000 R2V & U 1000 AR2V Power Cable
Nexus Cable U 1000 R2V & U 1000 AR2V Power Cable – view 2
Nexus Cable U 1000 R2V & U 1000 AR2V Power Cable
Nexus Cable U 1000 R2V & U 1000 AR2V Power Cable – view 2

U 1000 R2V & U 1000 AR2V Power Cable

Cable for industrial installations, building rising mains and low-voltage public lighting, with copper (R2V) or stranded aluminium (AR2V) conductor. Not recommended in ground flooded for more than two months per year.

 

Applications

Cable for industrial installations, building rising mains and low-voltage public lighting, with copper (R2V) or stranded aluminium (AR2V) conductor. Not recommended in ground flooded for more than two months per year.

Construction

  • Conductor: Solid or stranded copper — stranded aluminium (AR2V)
  • Insulation: XLPE
  • Filler: PVC
  • Sheath: Black PVC

Technical characteristics

  • Rated voltage: 1000 V
  • Conductor: Solid copper (S ≤ 6 mm²) class 1 — stranded copper (S ≥ 6 mm²) class 2 — stranded aluminium class 2 (AR2V)
  • Max. operating temperature: 85 °C continuous / 250 °C short circuit
  • Core identification — type A (with protective conductor): Brown-blue-G/Y; black-grey-brown-G/Y; black-blue-brown-grey-G/Y
  • Core identification — type B (without protective conductor): Brown-blue; black-blue-brown (1.5 and 2.5 mm²); brown-black-grey (≥ 4 mm²); black-blue-brown-grey
NFC 32-321